Logo
Nazad

Power Transformer Neutral Point Grounding Methods: Analysis of Fault Characteristics

The method of power transformer neutral point grounding is very important for power distribution network operation because it strongly affect the shapes and values of overvoltages and fault currents. Many methods of grounding are used in medium voltage (MV) power distribution networks. The selection of grounding method largely depends on the characteristics of power network connected to the substation. It is also necessary to consider the advantages and disadvantages of various neutral grounding methods during selection process to find the best solution from a technical and economical point of view. The effects of grounding methods on the characteristics of single-phase short circuit fault are discussed in this paper on the example of 110/20 kV substation ′′Bugojno′′. Modeling and simulation of the considered substation, power transmission and distribution lines are implemented in EMTP-RV software.