Parametric Analysis of Lightning Overvoltages in High-Voltage Gas Insulated Substation
Nearby lightning strokes are often considered as a prime source of transient overvoltages in the substations. Lightning overvoltages can cause unreliable operation of power system and power supply interruptions. Calculation of expected lightning overvoltages is necessary to design appropriate protection system. This paper presents the analysis of the lightning overvoltage performance of real 400 kV overhead transmission line and gas insulated substation (GIS), considering various factors, such as lightning stroke locations, peak currents, front rise times, etc. EMTP-RV software was used to model transmission line and substation elements and conduct simulations, while transmission line lightning performance was determined using Sigma Slp software. The expected overvoltages and surge arrester currents are calculated and used to design lightning protection system of the considered substation. Obtained results also indicate the importance of proper modelling of power system elements and lightning strokes.