Logo
Nazad

Identification of coherent-generator groups using the Huang ' s empirical mode decompositions and correlations between IMFs

Modern power systems are a very complex dynamical system spreading over a large geographical area. They indicate very complex phenomena in some parts as well as in the whole interconnected power system. In large and complex systems, there are coherent groups of generators. A group of generators in one area swings against a group of generators in another area. In this paper, using the Huang's Empirical Mode Decomposition (EMD) signals of the rotor-angle oscillations are separated into several Intrinsic Mode Functions (IMFs) and, thereafter, the correlations between IMFs are applied as a coherency measure and criterion for identification of coherentgenerator groups in a power system. The applied approach is analysed for the Kundur two area-four machines test system and New England (NE) bus 39 test system. A comparison between the results of NE bus 39 test system with those of other researches shows a high degree of similarity.