Logo
Nazad

Calculation of the Electric Field Intensity and Magnetic Flux Density Generated by High Voltage Overhead Transmission Lines

This paper considers calculation methods for the electric field intensity and magnetic flux density in the vicinity of the overhead transmission lines, as well as the calculation of alternating current (AC) corona onset electric field intensity. Calculations within this paper are made using the 2D algorithms of Charge Simulation Method (CSM) and Biot-Savart (BS) law based method. In order to obtain more accurate results, calculations are made by representing each overhead transmission line conductor with a large number of electric and magnetic field sources. By applying this approach, bundle conductors can be represented in a more realistic way and also singularity problems can be avoided when calculating electric field intensity. The presented methods are applied to a real overhead transmission line configuration, and obtained results are compared with field measurement results over the lateral profile. For considered overhead transmission line, AC corona onset electric field intensity is calculated and compared with calculated electric field intensity on the conductor’s surface. A comparison of calculated and measured results shows that considered calculation methods give satisfactory results.